DESCRIPTION
This DTC is stored if refrigerant pressure on the high pressure side is extremely low (176 kPa (1.8 kgf/cm2, 26 psi) or less) or extremely high (3025 kPa (30.8 kgf/cm2, 439 psi) or more). The air conditioning tube and accessory assembly (air conditioner pressure sensor), which is installed on the pipe on the high pressure side to detect refrigerant pressure, sends a refrigerant pressure signal to the air conditioning amplifier assembly. The air conditioning amplifier assembly converts this signal to a pressure value according to the sensor characteristics and uses it to control the compressor.
DTC No. | Detection Item | DTC Detection Condition | Trouble Area | Memory | Note |
---|---|---|---|---|---|
B1423 | Open in Pressure Sensor Circuit / Abnormal Refrigerant Pressure |
|
| - | - |
HINT:
The air conditioning amplifier assembly stores the DTC of the respective malfunction if it has occurred for the period of time indicated in the brackets.
WIRING DIAGRAM
CAUTION / NOTICE / HINT
NOTICE:
When the auxiliary battery is disconnected or the air conditioning amplifier assembly is replaced, be sure to perform servo motor initialization.
Click here
HINT:
If DTC B1423 and B14B8 are output at the same time, troubleshoot for DTC B14B8 first.
PROCEDURE
1. | CHECK AIR CONDITIONER PRESSURE SENSOR (POWER SOURCE CIRCUIT) |
(a) Disconnect the air conditioner pressure sensor connector. |
|
(b) Measure the voltage according to the value(s) in the table below.
Standard Voltage:
Tester Connection | Switch Condition | Specified Condition |
---|---|---|
A18-3 (+) - A18-1 (-) | Power switch on (IG) | 4.75 to 5.25 V |
NG | GO TO STEP 4 |
|
2. | CHECK AIR CONDITIONER PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT) |
(a) Remove the air conditioning amplifier assembly with the connectors still connected. Click here |
|
(b) Measure the voltage according to the value(s) in the table below.
Standard Voltage:
Tester Connection | Switch Condition | Specified Condition |
---|---|---|
I50-9 (PRE) - Body ground | Power switch on (IG) A/C switch off | 0.62 to 4.73 V |
HINT:
If the measured voltage is not within the normal range, there may be a malfunction in the air conditioning amplifier assembly, air conditioner pressure sensor, or wire harness. It is also possible that the amount of refrigerant may not be appropriate.
NG | GO TO STEP 11 |
|
3. | CHECK AIR CONDITIONER PRESSURE SENSOR (SENSOR SIGNAL CIRCUIT) |
(a) Measure the voltage when the following conditions are satisfied.
Item | Condition |
---|---|
Vehicle Doors | Fully open |
Temperature Setting | MAX COLD |
Blower Speed | Hi |
A/C Switch | On |
R/F Switch | Recirculation |
Interior Temperature | 25 to 35°C (77 to 95°F) |
NOTICE:
HINT:
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
(1) Measure the voltage according to the value(s) in the table below. Standard Voltage:
|
|
Result | Proceed to |
---|---|
OK (When troubleshooting according to the DTC) | A |
OK (When troubleshooting according to Problem Symptoms Table) | B |
NG | C |
A | REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY |
B | PROCEED TO NEXT SUSPECTED AREA SHOWN IN PROBLEM SYMPTOMS TABLE |
C | GO TO STEP 5 |
4. | CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING TUBE AND ACCESSORY ASSEMBLY [AIR CONDITIONER PRESSURE SENSOR]) |
(a) Disconnect the I50 air conditioning amplifier assembly connector.
(b) Disconnect the A18 air conditioning tube and accessory assembly (air conditioner pressure sensor) connector.
(c) Measure the resistance according to the value(s) in the table below.
Standard Resistance:
Tester Connection | Condition | Specified Condition |
---|---|---|
I50-10 (S5-3) - A18-3 (+) | Always | Below 1 Ω |
I50-10 (S5-3) or A18-3 (+) - Body ground | Always | 10 kΩ or higher |
OK | REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY |
NG | REPAIR OR REPLACE HARNESS OR CONNECTOR |
5. | CHECK COOLING FAN SYSTEM |
(a) Check that the cooling fan(s) operates normally.
Click here
NG | GO TO COOLING FAN SYSTEM |
|
6. | CHARGE SYSTEM WITH REFRIGERANT |
(a) Use a refrigerant recovery unit to recover refrigerant.
(b) Evacuate the air conditioning system.
(c) Add an appropriate amount of refrigerant.
Click here
HINT:
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC.
|
7. | CHECK FOR DTC |
(a) Check for DTC when the following conditions are satisfied.
Item | Condition |
---|---|
Vehicle Doors | Fully open |
Temperature Setting | MAX COLD |
Blower Speed | Hi |
A/C Switch | On |
R/F Switch | Recirculation |
Interior Temperature | 25 to 35°C (77 to 95°F) |
NOTICE:
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
HINT:
Result | Proceed to |
---|---|
DTC B1423 is not output | A |
DTC B1423 is output | B |
A | REPLACE COOLER CONDENSER ASSEMBLY |
|
8. | REPLACE COOLER EXPANSION VALVE |
(a) Replace the cooler expansion valve with a new one.
Click here
HINT:
Replace the cooler expansion valve with a new one because the expansion valve is either stuck or clogged.
|
9. | CHARGE SYSTEM WITH REFRIGERANT |
(a) Use a refrigerant recovery unit to recover refrigerant.
(b) Evacuate the air conditioning system.
(c) Add an appropriate amount of refrigerant.
Click here
HINT:
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC.
|
10. | CHECK FOR DTC |
(a) Check for DTC when the following conditions are satisfied.
Item | Condition |
---|---|
Vehicle Doors | Fully open |
Temperature Setting | MAX COLD |
Blower Speed | Hi |
A/C Switch | On |
R/F Switch | Recirculation |
Interior Temperature | 25 to 35°C (77 to 95°F) |
NOTICE:
If refrigerant pressure on the high pressure side becomes high, the DTC will be set. It is necessary to measure the voltage for a certain amount of time (approximately 10 minutes) because the DTC may be set after the air conditioning operates for a while.
HINT:
Result | Proceed to |
---|---|
DTC B1423 is not output | A |
DTC B1423 is output | B |
A | END (COOLER EXPANSION VALVE IS DEFECTIVE) |
B | CLEAN OR REPLACE COOLER CONDENSER ASSEMBLY |
11. | CHECK HARNESS AND CONNECTOR (AIR CONDITIONING AMPLIFIER ASSEMBLY - AIR CONDITIONING TUBE AND ACCESSORY ASSEMBLY [AIR CONDITIONER PRESSURE SENSOR]) |
(a) Disconnect the I50 air conditioning amplifier assembly connector.
(b) Disconnect the A18 air conditioning tube and accessory assembly (air conditioner pressure sensor) connector.
(c) Measure the resistance according to the value(s) in the table below.
Standard Resistance:
Tester Connection | Condition | Specified Condition |
---|---|---|
I50-9 (PRE) - A18-2 (PR) | Always | Below 1 Ω |
I50-9 (PRE) or A18-2 (PR) - Body ground | Always | 10 kΩ or higher |
NG | REPAIR OR REPLACE HARNESS OR CONNECTOR |
|
12. | CHECK FOR AIR CONDITIONING SYSTEM LEAK |
(a) Install a manifold gauge set.
(b) Recover the refrigerant from the air conditioning system using a refrigerant recovery unit.
(c) Evacuate the air conditioning system and check that vacuum can be maintained in it.
HINT:
If vacuum cannot be maintained in the air conditioning system, refrigerant may be leaking from it. In this case, it is necessary to repair or replace the leaking part of the air conditioning system.
Result | Proceed to |
---|---|
Vacuum can be maintained in the air conditioning system | A |
Vacuum cannot be maintained in the air conditioning system | B |
B | GO TO STEP 17 |
|
13. | CHARGE SYSTEM WITH REFRIGERANT |
(a) Use a refrigerant recovery unit to recover refrigerant.
(b) Evacuate the air conditioning system.
(c) Add an appropriate amount of refrigerant.
Click here
HINT:
If refrigerant is added and the system has not been properly evacuated (insufficient vacuum time), moisture in the air remaining in the system will freeze in the expansion valve, blocking the flow on the high pressure side. Therefore, in order to confirm the problem, recover the refrigerant and properly evacuate the system. Add an appropriate amount of refrigerant, and check for DTC.
|
14. | CHECK FOR DTC |
(a) Check for DTC when the following conditions are satisfied.
Item | Condition |
---|---|
Vehicle Doors | Fully open |
Temperature Setting | MAX COLD |
Blower Speed | Hi |
A/C Switch | On |
R/F Switch | Recirculation |
Interior Temperature | 25 to 35°C (77 to 95°F) |
NOTICE:
HINT:
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
Result | Proceed to |
---|---|
DTC B1423 is not output | A |
DTC B1423 is output | B |
A | END |
|
15. | CHECK AIR CONDITIONER PRESSURE SENSOR |
(a) Install a manifold gauge set.
(b) Turn the power switch on (IG).
(c) Measure the voltage according to the value(s) in the table below. Standard Voltage:
|
|
NG | REPLACE AIR CONDITIONING TUBE AND ACCESSORY ASSEMBLY (AIR CONDITIONER PRESSURE SENSOR) |
|
16. | CHECK FOR DTC |
(a) Check for DTC when the following conditions are satisfied.
Item | Condition |
---|---|
Vehicle Doors | Fully open |
Temperature Setting | MAX COLD |
Blower Speed | Hi |
A/C Switch | On |
R/F Switch | Recirculation |
Interior Temperature | 25 to 35°C (77 to 95°F) |
NOTICE:
HINT:
When the outside air temperature is low (below -1.5°C [29.3°F]), the compressor stops due to operation of the ambient temperature sensor and the evaporator temperature sensor to prevent the evaporator from freezing. In this case, perform the inspection in a warm indoor environment.
Result | Proceed to |
---|---|
DTC B1423 is not output | A |
DTC B1423 is output | B |
A | END |
B | REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY |
17. | REPAIR AIR CONDITIONING SYSTEM LEAK |
(a) Identify the area where refrigerant leaks from.
Click here
(b) Repair the identified area of the air conditioning system.
(c) Evacuate the air conditioning system.
NEXT | CHARGE SYSTEM WITH REFRIGERANT |